- Large Dual Display
- Independent Self-Tune for Each Zone
- Independent Fuzzy Logic for Each Zone
- Loop Break Protection
- Peak/Valley Indication
- Illuminated Keypad
- Four Password Protected Security Levels
The 32DZ Series temperature/process controls set
a new standard in 1/32 DIN power, flexibility, and value.
Love Controls is proud to be the creator of the world ’s
first dual zone control in the 1/32 DIN size. Ease of use
is assured from the creators of the world ’s first dual
display 1/32 DIN temperature /process control. The 32DZ
offers a semi-universal input (10 thermocouple types in
one of two groups, an RTD type, and voltage and current
types). Each zone offers a single set point with mechanical
relay, 5 VDC pulsed output, or AC SSR. One of the two outputs
may be a proportional 4 to 20 mA output that may be assigned
to either zone 1 or zone 2.Standard features include independent
Fuzzy Logic, Selftune, and Peak/Valley indication for each
zone.Process protection is provided by open sensor protection,
shorted sensor protection, input rate of change protection,
and loop break protection. Options for the 32DZ include
RS-485 Serial Communication and low voltage operation. Designed
and built in the USA, the 32DZ family of controls offers
the highest levels of features, function, and quality available
today.
32DZ
Series
|
Zone 1 Input and Zone 2 Input
1 = Thermocouple J,K,E,L,N
2 = Thermocouple T,R,S,B,C
4 = 1000 Ohm RTD
5 = Current, 0 or 4 to 20 mA
6 = Voltage, 0 to 10 V or 2 to 10 V
|
Output A
1 = SSR
2 = Switched Voltage 5 VDC
3 = Relay
5 = Proportional Current
8 = DC SSR
|
Output B
1 = SSR
2 = Switched Voltage 5 VDC
3 = Relay
8 = DC SSR
|
Series 32DZ Limit Control
Options
992, RS-485 Serial Communications. Allows remote
computer to read and write all control parameters
9502, 12-24 VDC/VAC 50-400Hz power supply (control
oper-ates on low voltage equipment)
PHYSICAL
DATA
Selectable Inputs: Thermocouple, RTD, DC Voltage
or DC Current selectable.
Display: Two 4-digit, 7 segment, 0.25" high (6.35
mm) LEDs.
Accuracy: ±0.25% of span, ±1 least significant digit.
Supply Voltage: 100 to 240 VAC, nominal, +10 - 15%,
50 to 400 Hz. single phase; 132 to 240 VDC, nominal, +10
- 20%.
Power Consumption: 5 VA maximum.
Operating Temperature: +14° to 131°F (-10°to +55°C).
Memory Backup: Nonvolative memory. No batteries required.
Control Output Ratings:
AC SSR: 0.75 A resistive @ 240 VAC at 77°F (25°C),
zero cross-over fired. Derates to 0.5 A @ 130°F (55°C).
DC SSR: 1.25 A @ 32 VDC at 77°F (25°C), maximum isolated.
Derates to 1.0 A @ 130°F (55°C).
Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240
VAC induc-tive;
Pilot Duty Rating: 250 VA, 2 A @ 120 VAC or 1 A @
240 VAC.
Current (Non-isolated): 0 to 20 mA (programmable)
across 600 ohms maximum.
Switched Voltage (Non-isolated): 5 VDC @ 20 mA.
Weight: 4 oz. (114 g).
INPUT
RANGES
INPUT TYPE |
RANGE °F |
RANGE °C |
Type J or L1 Thermocouple |
-100 to +1607 |
-73 to +871 |
Type K1 Thermocouple |
-200 to +2500 |
-129 to +1371 |
Type T1 Thermocouple |
-350 to +750 |
-212 to +398 |
Type E1 Thermocouple |
-100 to 1800 |
-73 to +932 |
Type R Thermocouple |
0 to 3200 |
-17 to +1760 |
Type S Thermocouple |
0 to 3200 |
-17 to +1760 |
Type B Thermocouple |
+75 to +3308 |
+24 to +1820 |
Type C Thermocouple |
0 to 4208 |
-17 to +2320 |
Type N1 Thermocouple |
-100 to +2372 |
-73 to +1300 |
1000 Ohm Plt. 0.00385 DIN1 RTD |
-328 to +1607 |
-200 to +875 |
Current/Voltage/.Voltage2 |
Scalable Units from -1999 to +9999 |
1 These Input Types can be set for 0.1° display.
If temperature goes aboeve 999.9° or less than -199.9° the
display will return to whole degree resolution.
2 The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC,
2 to 10 VDC, and -10 to +10 to mVDC inputs are fully scalable
from a minimum of 100 counts span placed anywhere within the
range of -1999 to +9999. Decimal point position is adjustable
from the zero place (9999), tenths (999.9), hundredths (99.99),
thousandths (9.999), or ten thousandths (.9999).