Temperature Process Controller from Dwyer Instruments

Temperature,Process,Controller

  • Large Dual Display
  • Independent Self-Tune for Each Zone
  • Independent Fuzzy Logic for Each Zone
  • Loop Break Protection
  • Peak/Valley Indication
  • Illuminated Keypad
  • Four Password Protected Security Levels

The 32DZ Series temperature/process controls set a new standard in 1/32 DIN power, flexibility, and value. Love Controls is proud to be the creator of the world ’s first dual zone control in the 1/32 DIN size. Ease of use is assured from the creators of the world ’s first dual display 1/32 DIN temperature /process control. The 32DZ offers a semi-universal input (10 thermocouple types in one of two groups, an RTD type, and voltage and current types). Each zone offers a single set point with mechanical relay, 5 VDC pulsed output, or AC SSR. One of the two outputs may be a proportional 4 to 20 mA output that may be assigned to either zone 1 or zone 2.Standard features include independent Fuzzy Logic, Selftune, and Peak/Valley indication for each zone.Process protection is provided by open sensor protection, shorted sensor protection, input rate of change protection, and loop break protection. Options for the 32DZ include RS-485 Serial Communication and low voltage operation. Designed and built in the USA, the 32DZ family of controls offers the highest levels of features, function, and quality available today.

32DZ Series

 
Zone 1 Input and Zone 2 Input
1 = Thermocouple J,K,E,L,N
2 = Thermocouple T,R,S,B,C
4 = 1000 Ohm RTD
5 = Current, 0 or 4 to 20 mA
6 = Voltage, 0 to 10 V or 2 to 10 V
Output A
1 = SSR
2 = Switched Voltage 5 VDC
3 = Relay
5 = Proportional Current
8 = DC SSR
Output B
1 = SSR
2 = Switched Voltage 5 VDC
3 = Relay
8 = DC SSR

Series 32DZ Limit Control

Options
992, RS-485 Serial Communications. Allows remote computer to read and write all control parameters
9502, 12-24 VDC/VAC 50-400Hz power supply (control oper-ates on low voltage equipment)

PHYSICAL DATA
Selectable Inputs: Thermocouple, RTD, DC Voltage or DC Current selectable.
Display: Two 4-digit, 7 segment, 0.25" high (6.35 mm) LEDs.
Accuracy: ±0.25% of span, ±1 least significant digit.
Supply Voltage: 100 to 240 VAC, nominal, +10 - 15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal, +10 - 20%.
Power Consumption: 5 VA maximum.
Operating Temperature: +14° to 131°F (-10°to +55°C).
Memory Backup: Nonvolative memory. No batteries required.
Control Output Ratings:
AC SSR: 0.75 A resistive @ 240 VAC at 77°F (25°C), zero cross-over fired. Derates to 0.5 A @ 130°F (55°C).
DC SSR: 1.25 A @ 32 VDC at 77°F (25°C), maximum isolated. Derates to 1.0 A @ 130°F (55°C).
Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC induc-tive;
Pilot Duty Rating: 250 VA, 2 A @ 120 VAC or 1 A @ 240 VAC.
Current (Non-isolated): 0 to 20 mA (programmable) across 600 ohms maximum.
Switched Voltage (Non-isolated): 5 VDC @ 20 mA.
Weight: 4 oz. (114 g).

INPUT RANGES

INPUT TYPE RANGE °F RANGE °C
Type J or L1 Thermocouple -100 to +1607 -73 to +871
Type K1 Thermocouple -200 to +2500 -129 to +1371
Type T1 Thermocouple -350 to +750 -212 to +398
Type E1 Thermocouple -100 to 1800 -73 to +932
Type R Thermocouple 0 to 3200 -17 to +1760
Type S Thermocouple 0 to 3200 -17 to +1760
Type B Thermocouple +75 to +3308 +24 to +1820
Type C Thermocouple 0 to 4208 -17 to +2320
Type N1 Thermocouple -100 to +2372 -73 to +1300
1000 Ohm Plt. 0.00385 DIN1 RTD -328 to +1607 -200 to +875
Current/Voltage/.Voltage2 Scalable Units from -1999 to +9999
1 These Input Types can be set for 0.1° display. If temperature goes aboeve 999.9° or less than -199.9° the display will return to whole degree resolution.
2 The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC, 2 to 10 VDC, and -10 to +10 to mVDC inputs are fully scalable from a minimum of 100 counts span placed anywhere within the range of -1999 to +9999. Decimal point position is adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), thousandths (9.999), or ten thousandths (.9999).